DIN 43709 Compliant
-
60mV output
-
±0.5% tolerance (class 0.5)
SPECIFICATIONS |
|||
Type |
Rated Current (A) * |
Operating Current (A) |
Resistance (mn) |
RSDIN-6000-60 |
6000 |
4000 |
0.010 |
Rated Output |
60mV Standard Custom outputs may be available on request |
||
Voltage Tolerance |
±0.5% Standard |
||
Operating Temp. |
+30°C to +70°C |
||
Storage Temp. |
-55°C to 80°C |
||
Materials / Torque Specification |
Resistance Elements |
Manganin |
|
Terminal Blocks |
Brass |
||
Primary Hardware Torque 311Nm |
Zinc plated steel Bolts, Nuts, Washers |
||
Secondary Hardware Torque 4.3Nm |
Zinc plated steel Screws, Washers M5x8 |
|
Operating Current Derating: For continuous operation, it is recommended that shunts are not run at more than two thirds (2/3) the rated current under normal conditions per IEEE standards for DC instrument shunts. At ambient tempera- tures above 40°C, the current must be further derated to prevent damage.